Environmental Energy Consumption = Temperature difference(T)In/Out ×Air exchange amount(M×Air heat capacity(C)* .

* Heat capacity is the measurable physical quantity that characterizes the amount of heat required to change a body’s temperature by a given amount, the measurable physical quantity that characterizes the amount of heat required to change a body’s temperature by a given amount. Here air capacity =1.2Kj/m3 .


▪  Take the city Hong Kong (China) as an example .

Average temperature is about 27 .

Inside temperature as human body comfortable level 20 .

A common star hotel with 500 rooms, 60%-80% occupancy rate, with 1.5 person in every room, hosting 450-600 guests everyday, whose average daily entry and exit is 4-5 times each, coming with 1800-3000 times entry and exit totally. Considering other factors such as other visitors or food takeout etc., we choose a random value as 4320 .


▪  About the Doors

Revolving Door with the diameter 3200mm and opening height 2200mm(Total height 2500mm, with canopy height 300mm).

Sliding Door with the opening width as 1700mm and height as 2200mm .


▪  Calculation for Air exchange amount – Sliding Door

Air Exchange Amount=Open area (A×Opening time (S)×Air movement(V)=3.74 x8640 x4.5 = 145,411.2 m3.

Note:

Opening area (A)=1.7×2.2=3.74m2.

Opening times (S) =8,640s/day.

Air movement(V) =4.5m/s .

*Assuming 3 persons each time, opening/closing hold time as 10 seconds if be converted to 60% of fully energy, leads to a result as: 4,320/3*10*0.6= 8,640 seconds every day.

*Air flow (v) =4.5m/s (Average wind speed in Hong Kong is about 5.5m/s per yearConsidering temperature difference and air-conditioning pressure, modify it to 4.5m/s).


▪  Calculation for Air exchange amount – Revolving Door

Air Exchange Amount= Air volumn (V) ×Revolving circles(N) =17.68448 x2,160 = 38,198.4768 m3.

Note:

Air volumn(V)= Cross-section(A) ×Height(H) =3.14×(3.2/2)2×2.2=17.68448m3.

Revolving times(n)=2,160r/d (rounds/day)

*4320 persons everyday6 person per roundsrevolving door revolves 2 rounds at high speed 4r/m when there is pedestrian and revolves 1 round at a low speed 2.5r/m when its vacant. So 4320/6 x(2+1)=2,160 r/d .


▪  Environmental Energy Consumption

* Sliding Door

Environmental Energy Consumption = Temperature difference(T)In/Out ×Air exchange amount(M×Air heat capacity(C) =7 x145,411.2 x1.2 =1,221,454.08 kj .

* Revolving Door

Environmental Energy Consumption = Temperature difference(T)In/Out ×Air exchange amount(M×Air heat capacity(C) =7 x38,198.4768 x1.2 =320,867.21 kj .

Note:

Temperature difference(T)In/Out =27-20=7 .

Air Heat Capacity =1.2kj/m3.


▪  Conclusion

1,221,454.08 /320,867.21=3.81 .

About the Environmental Energy Consumption between Sliding Door and Revolving Door, the former is over times that of the latter .